For large industrial motors, sleeve bearings are widely used because they can offer excellent performance in high-power and high-speed applications.
However, when a motor is required to meet an Ex d IIC T4 explosion-proof classification, customers may encounter an important limitation:
Sleeve bearings are not permitted for Group IIC flameproof rotating electrical machines under the applicable flameproof standards.
This often raises a question:
Why can a conventional high-voltage motor use sleeve bearings, while an Ex d IIC T4 explosion-proof motor may require rolling-element bearings?
The key reason is not simply bearing temperature.
It is related to the much stricter requirements for flameproof joints, shaft clearances, mechanical movement, and ignition containment in IIC hazardous gas environments.
What Does Ex d IIC T4 Mean?
Before discussing the bearing itself, it is useful to understand the explosion-proof marking.
Ex d means the motor uses a flameproof enclosure.
The enclosure is designed to withstand an internal explosion and prevent the flame or hot gases from igniting the explosive atmosphere outside the motor.
IIC is the most demanding gas subgroup within Group II gas environments.
Typical gases associated with IIC classification include hydrogen and acetylene.
Because these gases can ignite very easily and flame propagation is more difficult to contain, IIC equipment requires particularly strict flameproof construction.
T4 is the temperature class.
For T4 equipment, the maximum surface temperature is limited to 135°C under the applicable rated conditions.
Therefore, Ex d IIC T4 represents a combination of:
Flameproof protection
IIC gas group requirements
T4 surface temperature limitation
Is T4 the Reason Sleeve Bearings Are Not Allowed?
Not exactly.
This is an important distinction.
The restriction on sleeve bearings is fundamentally associated with the IIC flameproof construction, rather than simply the T4 temperature limit.
GB/T 3836.2-2021, the current Chinese standard for equipment protected by flameproof enclosure “d”, states that sleeve bearings are not permitted for Group IIC rotating electrical machines.
Equivalent requirements have also historically appeared in IEC 60079-1 for flameproof equipment.
Therefore, when a motor is specified as:
Ex d IIC T4
the critical bearing restriction comes from the Ex d IIC requirement.
T4 remains important for temperature control, but it is not the primary reason sleeve bearings are prohibited.
What Is a Flameproof Joint?
A flameproof motor is not designed to prevent an explosive gas mixture from ever entering the enclosure.
Instead, the enclosure is designed so that if ignition occurs internally:
The enclosure can withstand the explosion pressure.
Hot gases must pass through precisely controlled flameproof joints.
The flame is cooled and extinguished before reaching the surrounding hazardous atmosphere.
The dimensions of these flameproof joints are therefore extremely important.
Typical flameproof joints may exist around:
Motor end shields
Terminal boxes
Inspection covers
Shaft passages
Bearing housings
For the motor shaft, there must be a carefully controlled path between the rotating shaft and stationary housing.
This shaft area becomes particularly important when discussing bearing type.
Why Does Bearing Type Affect Flameproof Safety?
The bearing determines how accurately the rotor and shaft are positioned inside the motor.
A rolling-element bearing generally provides relatively well-controlled radial shaft positioning.
Sleeve bearings operate differently.
The shaft rotates on an oil film and requires a designed operating clearance between the shaft journal and bearing surface.
This means the shaft has a certain degree of movement within the bearing clearance.
Bearing wear, oil-film behavior, shaft movement, thermal expansion, and mechanical loading can all influence the actual shaft position.
For an ordinary motor, this movement can be completely acceptable.
For a flameproof IIC motor, however, shaft movement becomes much more critical because the shaft passes through a flameproof boundary.
Why Is IIC More Demanding?
Not all explosive gases behave in the same way.
IIC gases have particularly demanding flame-propagation characteristics.
This means the flameproof enclosure must control clearances much more strictly than for less demanding gas groups.
A flameproof shaft passage must maintain the required relationship between:
Shaft diameter
Radial clearance
Flamepath length
Bearing clearance
Rotor movement
Manufacturing tolerance
Bearing wear
If shaft movement becomes too large, the effective flameproof clearance may no longer remain within the certified design limits.
That is why bearing arrangement becomes part of explosion-proof safety rather than simply a mechanical design decision.
Why Are Sleeve Bearings More Difficult in This Situation?
Sleeve bearings require operating clearance.
The shaft does not remain perfectly fixed at one geometric center under all operating conditions.
Its position can vary depending on:
Oil-film thickness
Rotor weight
Shaft speed
External load
Bearing wear
Temperature
Lubrication condition
Start-up and shutdown conditions
This makes controlling the shaft-related flameproof clearance more complicated.
In a Group IIC environment, where the acceptable flameproof construction is especially restrictive, this additional shaft movement creates a safety challenge.
For this reason, the standard does not simply ask manufacturers to “make the clearance smaller.”
Instead, it prohibits sleeve bearings for Group IIC rotating electrical machines.
What Does the Standard Require for Sleeve Bearings in Other Gas Groups?
This does not mean that sleeve bearings can never be used in explosion-proof motors.
For flameproof motors outside Group IIC, standards contain specific construction requirements for sleeve-bearing shaft arrangements.
For example, the flameproof joint associated with the shaft gland must satisfy defined dimensional requirements.
Where cylindrical or labyrinth flameproof joints are used with sleeve bearings, additional measures such as non-sparking materials may also be required under specified conditions.
So the correct statement is:
Sleeve bearings can be used in some flameproof motor designs, but they are not permitted for Group IIC rotating electrical machines under this flameproof construction requirement.
Why Are Rolling Bearings More Suitable for Ex d IIC Motors?
Rolling-element bearings such as ball bearings and roller bearings provide more predictable shaft positioning.
Their internal clearance can be controlled through:
Bearing selection
Manufacturing tolerances
Shaft fits
Housing fits
Bearing preload or arrangement
Axial positioning design
For flameproof rotating machines using rolling bearings, the standard also places requirements on the maximum radial clearance associated with the shaft gland arrangement.
This makes it easier to maintain a certified and repeatable flameproof shaft structure.
As a result, rolling bearings are commonly used in Ex d IIC T4 motors.
Is Sleeve Bearing Temperature Also a Concern?
Temperature is still important, but it is a separate issue.
Any Ex d IIC T4 motor must keep relevant external surface temperatures within the T4 limit.
Bearing temperature, lubrication temperature, motor losses, ambient temperature, and load conditions may all contribute to the overall thermal assessment.
However, even if engineers could demonstrate that a sleeve bearing operates well below 135°C, that alone would not solve the IIC restriction.
The problem is not simply:
“The sleeve bearing may become too hot.”
The more accurate explanation is:
“The sleeve-bearing shaft arrangement cannot be used for a Group IIC rotating electrical machine under the applicable flameproof construction requirements.”
What About Oil Leakage from Sleeve Bearings?
Sleeve bearings normally use lubricating oil.
Oil management can introduce additional engineering considerations, including:
Oil leakage
Oil seals
Lubrication systems
Piping
External oil units
Maintenance requirements
These factors can complicate an explosion-proof motor installation.
However, oil leakage is not the fundamental reason why Group IIC flameproof motors prohibit sleeve bearings.
The primary technical issue is compliance with the flameproof shaft and bearing construction requirements.
Why Are Sleeve Bearings Common in Large Non-IIC Motors?
Sleeve bearings still have major advantages for large motors.
They are often used in:
Large high-voltage motors
High-speed motors
Compressors
Large fans
Pumps
Petrochemical equipment
Their advantages may include:
High load capability
Long operating life
Good vibration performance
Suitability for large shaft diameters
Good performance at high speed
Stable continuous operation
Therefore, using rolling bearings instead of sleeve bearings in an Ex d IIC motor does not mean sleeve bearings are mechanically inferior.
It means that the explosion-protection requirement places additional constraints on the motor structure.
Can an Ex d IIB Motor Use Sleeve Bearings?
Potentially, yes.
IIB is less restrictive than IIC regarding flameproof gas-group requirements.
Sleeve-bearing flameproof motors may therefore be technically possible for certain IIB designs, provided the complete motor structure complies with the applicable standard and certification requirements.
However, this cannot be decided only from the bearing itself.
The complete motor must be designed, tested, and certified with the required:
Explosion-proof type
Gas group
Temperature class
Bearing arrangement
Shaft flamepath
Cooling method
Motor frame
A manufacturer should therefore confirm the available certified configuration.
Can a Standard Sleeve-Bearing Motor Simply Be Modified to Ex d IIC T4?
No.
Explosion-proof certification applies to the complete certified motor design.
It is not sufficient to take a standard sleeve-bearing high-voltage motor and simply add:
An explosion-proof terminal box
Thicker housing
A different nameplate
Flameproof markings
The motor's:
Housing
Shaft passages
Bearing structure
Flameproof joints
Terminal enclosure
Fasteners
Clearances
Temperature rise
Surface temperature
must all comply with the applicable explosion-protection requirements.
Therefore, bearing type can directly affect whether a motor can obtain a particular explosion-proof certification.
Ex d IIC T4 vs Sleeve Bearing: Key Points
| Item | Requirement / Effect |
|---|---|
| Ex d | Flameproof enclosure must contain internal explosion |
| IIC | Most demanding common Group II gas subgroup |
| T4 | Maximum surface temperature 135°C |
| Sleeve bearing | Allows designed shaft movement within oil-film clearance |
| Main issue | Maintaining compliant flameproof shaft construction |
| IIC requirement | Sleeve bearings are not permitted for Group IIC rotating machines |
| Common alternative | Rolling-element bearing arrangement |
What Should Customers Check During Motor Selection?
When specifying a large explosion-proof motor, customers should provide the exact explosion-proof requirement at the beginning of the project.
Important information includes:
Ex protection type
Gas group
Temperature class
Zone
Motor power
Voltage
Speed
Mounting arrangement
Driven equipment
Radial and axial loads
Required bearing type
Cooling method
Ambient temperature
This is especially important if the original motor uses sleeve bearings.
If the replacement motor is required to meet Ex d IIC T4, the original sleeve-bearing arrangement may not be directly transferable to the new motor.
The manufacturer may need to propose a rolling-bearing design instead.
Conclusion
Why can't an Ex d IIC T4 explosion-proof motor use sleeve bearings?
The main reason is not that sleeve bearings are weak, unreliable, or simply too hot.
The key issue is flameproof safety.
In an Ex d motor, the shaft passage forms part of the flameproof construction.
Sleeve bearings require operating clearance and allow a degree of shaft movement, making flameproof clearance control more complicated.
For Group IIC environments, where flameproof requirements are especially stringent, the applicable standard therefore does not permit sleeve bearings in rotating electrical machines.
T4, meanwhile, specifies a maximum equipment surface temperature of 135°C; it is an important thermal requirement, but it is not the fundamental reason for the sleeve-bearing restriction.
Therefore, when a large motor requires both:
Ex d IIC T4 certification
and
sleeve bearings
these two requirements may conflict.
The motor manufacturer should confirm the explosion-proof standard and certified bearing arrangement before finalizing the motor design.