Taking a three-phase asynchronous motor as an example, when the motor is started directly, the starting current will reach 5 to 7 times the rated current, and the starting torque can reach 1.2 to 1.3 times the rated torque. Because a larger current will cause the motor winding to overheat, and at the same time, a larger torque is not good for the motor body and the driven equipment. However, if the inverter is combined with the motor, the characteristics of the motor starting will be restricted by the inverter, and the starting torque, starting current and starting time will change. During the starting process, the current upper limit is generally set at 1.2 to 1.5 times the rated current. The corresponding acceleration torque is smaller than that of direct starting, so the corresponding starting time will be relatively longer. In the process of variable frequency starting, it is actually a process of gradually increasing synchronous speed, so it will be relatively stable when starting; for motors that are directly started at industrial frequency, at the moment of starting, it will be obvious that the motor has a larger shake, especially for small-sized high-speed motors, some of which have a direct feeling of jumping.

In the process of matching the motor and the inverter, the capacity selection of the inverter is crucial. If the inverter is too small, the motor will not be able to start. On the contrary, when the inverter capacity is too large, it is not conducive to the effective protection of the motor. General inverters have protection functions. The inverter itself has surge, overload, regenerative overvoltage, undervoltage, ground overcurrent, cooling fan abnormality, overheating and short circuit protection, and the motor has overload and overspeed protection; the entire control system has stall overcurrent and stall regenerative voltage protection functions. Different motor types and different load characteristics should be equipped with appropriate inverters; the performance levels of inverters of different qualities are also different. In particular, when the inverter performance is poor, it will have adverse effects on the motor, such as electromagnetic noise and electromagnetic vibration caused by high-order harmonics, and specific problems such as motor shaft current that may be caused.